LUCN guaranteed to provide you with hosting services, and unified all of the client-server 7 * 24 hour management, network services on the server monitor, LUCN place according to the customer about the number of different server, to provide minimum 1 / 4 rack, to the whole rental counter integer programs to ensure good standards of space heat and electricity supply; according to the needs of customers with different grades of port sharing, exclusive bandwidth services. LUCN room is located in downtown Los Angeles, where the One Wilshire Building, 30 storeys tall, an area of 656,000 square feet, is the concentration of data exchange network in North America, the Pacific Rim's leading communications hub, is an international brand within the telecommunications industry and the U.S. Western single most important network connection point. One Wilshire Building, the United States and the global telecommunications industry, almost all market leaders belongs to, has now covering more than 240 telecom service providers, including: AT & T, Broadwing, Cable & Wireless , Worldcom, PacBell, Qwest, Communications, Sprint, Time Warner, Verizon and XO Communications and so on.
Standard telecom space:
- 1. "Original" standard space and semi-variable space.
- 2. Meet with generators and UPS uninterruptible power supply.
- 3. Meet with generators and UPS uninterruptible power supply.
- 4. Multi entry and multi-fiber providers.
- 5. Customizable Shell Space.
Wireless connection:
- 1. abinets and cages close to the roof.
- 2. Roof space to receive microwave, PCS and other antennas throughout Los Angeles.
- 3. MDF service virtual connection to the Meet Me Room and air conditioning suites.
- 4. Wire connected to the Meet Me Room.
- 5. Devices: DMS 250/300 international gateway switch.
Civil parameters:
- 1. Structure: Steel frame concrete slab and fire.
- 2. Floor load: vertical load is 70 per square foot pounds, the earthquake load is 20 pounds per square foot
- 3. Ceiling Height: 15 feet (ground to top.)
- 4. Column spacing: 29 feet.
- 5. Electrical Capacity: per square foot 25W, upgrade to the 75W psf, 480V, 3 phase, 4 wire.
Main power supply:
- 1. Main power: 100W of power per square foot, all power by the different 480V, 3 phase, 4 wire bus tube transport. Consists of three 3750KVA, 480V transformer and a 5000KVA, 4160V transformers and extra 3750KVA transformer.
- 2. Emergency Power Supply: There are eight generators and a 470KW 2000KW generator in service interruptions or low voltage conditions to support the tenants of the main power. Power by 480V, 3 phase, 4 wire bus tubes (each generating a bus control) for distribution.
- 3. Fuel Storage: existing fuel storage and associated pumping about 21,000 gallons of diesel oil and filter stations. This will provide sufficient fuel storage capacity, so that all generators in the case without refueling for 24 hours of work.
Air Conditioning:
- 1. Building has two cooling systems, the first set of cooling equipment on the third floor roof, heat per square foot 75W.
- 2. Second set of more advanced new closed loop cooling system in the 30th floor roof, including 1,200 tons of excess cooling towers, piped to a higher level.